overspeed-protection-systems-with-triple-channel-redundancy-tmr.png

“State of the art” Overspeed Protection Systems with triple channel redundancy (TMR)

The focus of our production is in monitoring and protection systems for the protection of all type of “Rotating Equipment” and “Turbomachinery”. This includes the protection of turbines, compressors and expanders against overspeed trip and other criteria such as emergency stop, overpressure and overheating. Our claim is to be the world’s technological market leader in this field.

BRAUN Protection Systems with their TMR architecture monitor this equipment and guarantee the trouble-free operation of safety-critical applications “Rotating Equipment”. To ensure the safety of plant and personnel, this may be implemented with safety level SIL3.

Single Channel devices utilizing 1oo1 or 1oo2 do not ensure continued operation of the monitored machinery. In such cases, fault detection results in operational shutdown.

However, with Triple Channel redundancy incorporating 2oo3 evaluation, this is not the case. When system shutdown is not an option, our globally unique and true 2oo3 architecture provides the most comprehensive protection against spurious alarm signals and thus ensures continuous operation. This concept incorporates the monitoring of each trip criterion within each of the three Monitors in 2oo3, not only for the complete system. Integrated and sophisticated self-tests guarantee stable and continuous availability of the protection system.

Products of our competitors may release an unjustified shutdown of your machines – our systems keep your machines up and running.

E16 System product matrix (overview), Standard solutions in 2oo3 architecture

Model SIL3 SIL2 PFD Value Test
Interface
Test
Generator
Automatic
Test of 2oo3
Solenoid
by E16
PROFIBUS
Interface
E16x342   7,71 · 10-5     1
E16x352   7,71 · 10-5     2
E16x346   8,41 · 10-6   1
E16x356   8,41 · 10-6   2
E16x442   1,81 · 10-4     1
E16x452   1,81 · 10-4     2
E16x446   2,51 · 10-5   1
E16x456   2,51 · 10-5   2

 

Protection Systems for highest safety requirements up to SIL 3

E16x342

Monitoring and Protection System E16x342 for highest safety requirements up to SIL3

  • TMR (triple-modular-redundant) system with sensor monitoring and self-test
  • Highest safety levels with maximum availability by globally unique and true 2oo3 architecture for each trip criterion within each of the three Monitors
  • Maintenance-free during lifetime due to integrated automatic proof tests
  • External test of a 2oo3 solenoid valve block possible via the control system
  • Minimal Total Cost of Ownership
  • Requires less than 8% of the permissible PFD value for a SIL3 Safety Loop
  • Replacement of all active components during operation (Hot Swap)
  • TÜV certified for SIL3 / IEC 61508:2010
  • TÜV certified for PL e; Cat. 3 / DIN EN ISO 13849-1:2008
  • TÜV certified for SILCL3 / IEC 62061:2005
  • API670 and API612 compliant
  • 1 PROFIBUS Interface

E16x352

Monitoring and Protection System E16x352 for highest safety requirements up to SIL3

  • TMR (triple-modular-redundant) system with sensor monitoring and self-test
  • Highest safety levels with maximum availability by globally unique and true 2oo3 architecture for each trip criterion within each of the three Monitors
  • Maintenance-free during lifetime due to integrated automatic proof tests
  • External test of a 2oo3 solenoid valve block possible via the control system
  • Minimal Total Cost of Ownership
  • Requires less than 8% of the permissible PFD value for a SIL3 Safety Loop
  • Replacement of all active components during operation (Hot Swap)
  • TÜV certified for SIL3 / IEC 61508:2010
  • TÜV certified for PL e; Cat. 3 / DIN EN ISO 13849-1:2008
  • TÜV certified for SILCL3 / IEC 62061:2005
  • API670 and API612 compliant
  • 2 PROFIBUS Interfaces

E16x346

Monitoring and Protection System E16x346 for highest safety requirements up to SIL3

  • TMR (triple-modular-redundant) system with sensor monitoring and self-test
  • Highest safety levels with maximum availability by globally unique and true 2oo3 architecture for each trip criterion within each of the three Monitors
  • Maintenance-free during lifetime due to integrated automatic proof tests
  • Automated tests of a 2oo3 solenoid valve block with permanent monitoring of the feedback via the test generator
  • Minimal Total Cost of Ownership
  • Requires less than 1% of the permissible PFD value for a SIL3 Safety Loop
  • Enhanced safety values due to an integrated test generator
  • Replacement of all active components during operation (Hot Swap)
  • TÜV certified for SIL3 / IEC 61508:2010
  • TÜV certified for PL e; Cat. 3 / DIN EN ISO 13849-1:2008
  • TÜV certified for SILCL3 / IEC 62061:2005
  • API670 and API612 compliant
  • 1 PROFIBUS Interface

E16x356

Monitoring and Protection System E16x356 for highest safety requirements up to SIL3

  • TMR (triple-modular-redundant) system with sensor monitoring and self-test
  • Highest safety levels with maximum availability by globally unique and true 2oo3 architecture for each trip criterion within each of the three Monitors
  • Maintenance-free during lifetime due to integrated automatic proof tests
  • Automated tests of a 2oo3 solenoid valve block with permanent monitoring of the feedback via the test generator
  • Minimal Total Cost of Ownership
  • Requires less than 1% of the permissible PFD value for a SIL3 Safety Loop
  • Enhanced safety values due to an integrated test generator
  • Replacement of all active components during operation (Hot Swap)
  • TÜV certified for SIL3 / IEC 61508:2010
  • TÜV certified for PL e; Cat. 3 / DIN EN ISO 13849-1:2008
  • TÜV certified for SILCL3 / IEC 62061:2005
  • API670 and API612 compliant
  • 2 PROFIBUS Interfaces

 

Protection Systems for increased safety requirements up to SIL 2

E16x442

Monitoring and Protection System E16x442 for increased safety requirements up to SIL2

  • TMR (triple-modular-redundant) system with sensor monitoring and self-test
  • Highest safety levels with maximum availability by globally unique and true 2oo3 architecture for each trip criterion within each of the three Monitors
  • Maintenance-free during lifetime due to integrated automatic proof tests
  • External test of a 2oo3 solenoid valve block possible via the control system
  • Minimal Total Cost of Ownership
  • Requires less than 8% of the permissible PFD value for a SIL2 Safety Loop
  • Replacement of all active components during operation (Hot Swap)
  • SIL2 / IEC 61508:2010 compliant
  • API670 and API612 compliant
  • 1 PROFIBUS Interface

E16x452

Monitoring and Protection System E16x452 for increased safety requirements up to SIL2

  • TMR (triple-modular-redundant) system with sensor monitoring and self-test
  • Highest safety levels with maximum availability by globally unique and true 2oo3 architecture for each trip criterion within each of the three Monitors
  • Maintenance-free during lifetime due to integrated automatic proof tests
  • External test of a 2oo3 solenoid valve block possible via the control system
  • Minimal Total Cost of Ownership
  • Requires less than 8% of the permissible PFD value for a SIL2 Safety Loop
  • Replacement of all active components during operation (Hot Swap)
  • SIL2 / IEC 61508:2010 compliant
  • API670 and API612 compliant
  • 2 PROFIBUS Interfaces

E16x446

Monitoring and Protection System E16x446 for increased safety requirements up to SIL2

  • TMR (triple-modular-redundant) system with sensor monitoring and self-test
  • Highest safety levels with maximum availability by globally unique and true 2oo3 architecture for each trip criterion within each of the three Monitors
  • Maintenance-free during lifetime due to integrated automatic proof tests
  • Automated tests of a 2oo3 solenoid valve block with permanent monitoring of the feedback via the test generator
  • Minimal Total Cost of Ownership
  • Requires less than 1% of the permissible PFD value for a SIL2 Safety Loop
  • Enhanced safety values due to an integrated test generator
  • Replacement of all active components during operation (Hot Swap)
  • SIL2 / IEC 61508:2010 compliant
  • API670 and API612 compliant
  • 1 PROFIBUS Interface

E16x456

Monitoring and Protection System E16x456 for increased safety requirements up to SIL2

  • TMR (triple-modular-redundant) system with sensor monitoring and self-test
  • Highest safety levels with maximum availability by globally unique and true 2oo3 architecture for each trip criterion within each of the three Monitors
  • Maintenance-free during lifetime due to integrated automatic proof tests
  • Automated tests of a 2oo3 solenoid valve block with permanent monitoring of the feedback via the test generator
  • Minimal Total Cost of Ownership
  • Requires less than 1% of the permissible PFD value for a SIL2 Safety Loop
  • Enhanced safety values due to an integrated test generator
  • Replacement of all active components during operation (Hot Swap)
  • SIL2 / IEC 61508:2010 compliant
  • API670 and API612 compliant
  • 2 PROFIBUS Interfaces